Transmitters
SD-1RI (TYPE HS)
SD-1OX
SD-1EC
Hydrogen Specific
GD-70D
S2 Series
M2A
SD-1
2X Series
1X Series
XT Series
Hydrogen Specific
RKI offers unique proprietary sensor technologies for Hydrogen specific Detection in either the % LEL or PPM ranges. By utilizing a proprietary molecular sieve coating that is built into both our Catalytic or Solid state sensors, false alarms from typical Hydrocarbon interfering gases are essentially eliminated.
For the LEL range, a special catalytic sensor is coated with a molecular sieve that eliminates the response to common background gases like IPA, Methane, Gasoline, etc. while providing a Detection range of 0 - 100% LEL for Hydrogen.
The Hydrogen PPM sensor can reliably detect leaks 20 times smaller than a standard catalytic sensor. This solid state sensor has a molecular sieve coating on the sensing element, which filters out interference from other gases and provides a 0 - 2,000 PPM range. Both the LEL and PPM range sensors are available with 24 VDC transmitters with linear 4-20 mA outputs.
- Features
- Applications
- Approvals
- Specification
- Accessories
- Explosion proof housing and sensor design
- H2 specific solid state sensor for 0 - 2000 ppm
- H2 specific catalytic sensor for 0 - 100%LEL
- Molecular sieve filter built in; highly specific to H2
- Eliminates false alarms from IPA and other gases
- 4-20 mA transmitter, 24VDC
- Semiconductor
- Power Plants
- Fuel Cell Industry
- R & 0 applications
- Gas plants
- Indoor or outdoor. Explosion proof for Class
- Div. 1, Groups B, C, and D.
Part # | H2 Specific LEL 65-2450RK |
H2 Specific ppm 65-2440RK |
---|---|---|
Detection Range | 0-100% LEL | 0- 2000 ppm |
Min Operating Voltage | 11 VDC | |
Max Operating Voltage | 30 VDC | |
Max Current Draw | 200 mA (power wires) 25 mA (signal wires) 3 wires |
100 mA (power wires) 25 mA (signal wires) 3 wires |
Signal Output | 4 mA at 0% LEL 20 mA at 100% LEL Linear Output |
4 mA@ 0 ppm 20 mA @ 2000 ppm Linear Output |
Response Time | 20 Seconds to 90% concentration | 20 Seconds to 90% concentration |
Operating Environment | ||
Location | Indoor or outdoor. Explosion proof for Class 1. Div. 1, Groups B, C, and D. | |
Temperature | -40 to 180° F | 15 to 110° F |
Humidity | 5-95% RH non-condensing | |
Housing | Enclosure : Aluminum Explosion Proof | Sensor : Stainless steel and aluminum |
Sensor | ||
Type | Catalytic combustion with molecular sieve | Metal oxide semiconductor with molecular sieve |
Life Expectancy | Over 3 years typical | Over 5 years typical |
Controls | ||
Sensor Current | Factory set and sealed | |
Zero | Sets transmitter output to 4 mA with 0% LEL output from combustible sensor | Sets transmitter output to 4 mA with o ppm output from sensor |
Span | Sets transmitter output to 20 mA with 100% LEL output from combustible sensor | Sets transmitter output to 20 mA with 2000 ppm Hydrogen output from sensor |
Tools Needed | Calibration kit, Screwdriver, and voltmeter used to make adjustments. | |
Calibration Frequency | 6 Months | 12 Months |
Warranty | One year on electronics and sensors |
Specifications subject to change without notice.
- Mounting Bracket / Stand
- Weather Proof Canopy
- Trilog Software
- Repeater Panel
- Auto Dialer
- Water / Dust / Solvent Filter
- Belt
-
Flame Proof Flasher
-
Safe Area Hooter