Mumbai (HO) | New Delhi | Chennai | Kolkata | Hyderabad | Ankleshwar
SF6 Purity Analyser
SF6 (Sulfur hexafluoride) GAS PURITY ANALYSER FI-8000-SF6
SF6 is known for its high electric insulating characteristic, and it is widely used as an insulating gas in power substation facilities, electric transformers and electric current breakers. SF6 is known as greenhouse gas, its greenhouse effect is regarded 23500 times higher than CO2.Reduction of SF6 discharge volume, gas recovery and recycling is seriously required.
Riken manufactures SF6 Gas Purity Analyser, Model FI-8000-SF6 SF6 purity monitoring for gas recovery and gas recycling In compliance with SF6 RECYCLING GUIDE (CIGRE).
- Features
- Specification
- Accessories
- Minimum gas quantity for measuring
Gas measuring can be done with a small amount of gas quantity
Estimated gas consumption: Approx. 62.5ml (Sample pressure: 0.7MPa) - Simple operation
Pressure and flow rate adjustment is not necessary. - Data logger function
Max. 256 measuring data (date/time/measured value) can be stored - Small and compact design
Compact carrying case enables users to carry the instrument easily
Model | FI-8000-SF6 |
Target gas | SF6 (AIR base) |
Reference gas | AIR |
Principle | Interferometer (Optical sensor) |
Measuring range | 0.0 to 99.9%up |
Minimum resolution | 0.1% |
Accuracy | ±1% (Under same condition) |
Display | LCD (7 segment for value + Symbol + 20 segment for letter x 2 line) |
Gas sample pressure | 0.1~0.7MPa (Gauge pressure) |
Flow / rate | Approx. 250ml/min (Gas sample pressure is 0.7MPa) |
Power supply | AA battery x 3 pcs or AC adaptor (Optional accessory) |
Operation time | More than 16 hours (No alarm, no light at 25 ℃) |
Temperature & humidity range | -10 to 40℃ (no sudden change) Below 95%RH (no condensing) |
Outer dimension | Approx. 305 (W) ×270 (H) ×194(D) mm |
Weight | Approx. 4.5kg |
Function | Pressure compensation, Temperature compensation |
Accessories
-
Sampling Tube
-
Gas Inlet Socket
-
Battery
Optional Accessories
-